E²T Quasar M8100SM

QUASAR M8100SM-EXP废气燃烧烟道烟雾监测仪可持续监测几乎任何环境条件下附近最远0.25英里(400米)区域内废气燃烧烟道的烟雾水平,适用于自动烟雾控制系统,用以确保废气燃烧烟道的烟雾排放符合EPA所规定的标准。

E2T Quasar M8100PM View

Key Features

  • Flame detection up to 400 m
  • Detection of hydrocarbon as well as hydrogen flames
  • CSA/US and ATEX explosion-proof housing
  • Safety and environmental protection
  • Automatic gain control for adverse weather conditions
  • High quality sight-through optics
  • On-board alarm set point relay
  • Modular opto-electronic package for easy removal from housing
  • IR pyrometer and amplification circuitry in one single module

Details

QUASAR监测仪采用双波长红外检测系统以及电子电路的技术,可自动弥补由于雨天、下雪、雾天等造成的信号变化。所观测到的烟雾水平通过一个4-20 mA的信号进行传输,其报警设定点具有可调延迟时间的功能。QUASAR监测仪可安装在控制中心屋顶上,瞄准并监测远处废气燃烧烟道的烟雾水平。此外,监测仪还可安装在一个坚固的支架系统上,以抵抗强风造成仪器移位,同时还具有游标瞄准功能,可方便地实现长距离的物体瞄准。

QUASAR M8100SM-EXP的所有电气和光学部件都安装在一个经由CSA和CENELEC认证的外壳内,其危险场所分类为第一类、第一部分、第C、D组;第一类、第二部分、第A-D组;以及EExd IIB T4。安装在防爆外壳内的单个可替换使用的模块组件包含了所有电气和光学部件,便于监测仪的拆除与更换,且不会影响任何外部连接。


模块化的设计与单个的远程定位系统相结合,使QUASAR监测仪易于安装、维护并与其他系统相兼容,成为了最经济的废气燃烧烟道废气监测仪之一。

资料

Technical Data

 

Performance  

Working Distance:

0 to 1320 feet (400 m) 

Flame Type: Multi-wavelength infrared monitor sensitive to all flame including Hydrogen 
Field of View: Available in 37.5:1, 60:1, 75:1, 150:1 & 300:1 

Output Signal:

4 or 20 mA switched output

(4 mA = flame and 20 mA = no flame)

Alarm Setpoint: Mechanical relay
Response Time: 10 mS
Alarm Output Delay: 2 s to 2 min (Std) 
Sensitivity Adjustment:  Automatic climate compensation and manual gain for easy system setup
Electrical 
Power requirements: Available in 115 VAC or 230 VAC or 24 VDC (Voltages +/- 10%) 115 Watts
Physical Characteristics   
Dimensions: 

10.5 x 12.5 x 8.5 in (27 x 32 x 22 cm) 

Weight:  48 lbs (22 kg) 

Status Lights:

Green and red 

Mounting: 

M-3 heavy duty 360° swivel mount 

Environmental Specifications 

Ambient Temperature Limits:

-40 to 140 °F (-40 to 60 °C) with no cooling and using internal heater

If the equipment is used at the ambient temperature above +60 °C, before turning on the equipment, the cooling system shall be verified that the ambient temperature does not rise above +60 °C

Explosion-Proof Certification: CSA/US: Class 1, Division 1, Groups C and D Class 1, Division 2, Groups A through D, T4 CENELEC: EEx d IIB T4

Environmental Protection: 

Type 4X

 

查找您当地的代理

查找产品服务或买一台新的仪器.

全方位服务和支持

查找所有现场服务选项和资产保障.